Advantages of the plan:

▶ Commonly used single pump water supply function

Sleep/Wake up function: Sleep according to frequency, wake up according to pressure

Pipeline overpressure alarm function

PID feedback disconnection protection function

▶ Improve usability

After selecting the water supply macro, configure the state parameters: output frequency, set pressure, feedback pressure, output current, analog feedback AI2 value

Press the shift key to switch the above state parameters

After selecting the water supply macro, rotating the potentiometer can adjust the given pressure and has anti misoperation function

The unit of water supply pressure is kilogram force (bar), which is convenient for customers to use.

 

 

Special macro parameters and wiring instructions for constant pressure water supply

The PP-01=30 parameter is initialized as a dedicated macro for constant pressure water supply. The following parameters are default parameters for specialized macros, and necessary adjustments should be made according to the actual situation during use.

Frequency source setting

Parameter

Name

Setting Range

P0-02

Command source selection

1: Terminal commands

P0-03

Frequency source selection

8PID

P4- 18

AI curve 2 minimum input

2 .00V

P4-23

AI curve 3 minimum input

2 .00V

P7-03

Run display parameter 1

8001HMonitor operating frequency and pressure setting values

P7-04

Run display parameter 2

0001HPressure feedback value

P7-05

Shutdown display parameters

0800HPressure setting value

When the monitoring parameters are set pressure or feedback pressure, and the pressure setting source is PA-01, pressing the increase/decrease keys on the operation panel will enter PA-0 1 parameter modification mode. The operation and parameter modification modes are the same, and when it exits, it returns to the monitoring state.

PA-00

PID Set Source

0PA-01Setting

PA-01

PID  Digital settings

50 .0   0~ PA-04(Decimal places set by PA-14)

PA-02

PID Feedback source

0AI1(Remote pressure gauge) (default).

1: AI2  (For the S300 series, when the sensor is a 4-20mA pressure transmitter).

2: AI3  (For the S500 series, when the sensor is a 4-20mA pressure transmitter).

PA-04

PID given feedback range

0~65535 The default value is 100. 0

PA- 14

PID feedback range given decimal places

0-4

P8-49

Wake up pressure deviation

75 .0%

P8-50

Wake up delay time

20 .0s

P8-51

Sleep frequency

30Hz(When in sleep, the running light is flashing)

P8-52

Sleep delay time

100 .0s (Start timing after the PID reaches balance, otherwise it will enter sleep mode during the acceleration process)

PA-26

PID feedback loss detection value

5 .0%

PA-27

PID feedback loss detection time

10 .0s (Timing only starts after running)

Hardware wiring: DI1: Forward running FWD DI3: Fault reset (RESET) T1A-T1B-T1C: Fault output

Remote pressure gauge

10V AI1

GND

 

Pressure transmitter

 

24V

AI2(4 -20mA

 

pressure transmitter

24V

AI3(4 -20mA

COM

GND